Die Rolle der Hauptkomponenten des Kühltrockners

1. Kühlkompressor

Kühlkompressoren sind das Herzstück des Kühlsystems, und die meisten Kompressoren verwenden heute hermetische Hilfskompressoren. Raising the refrigerant from low to high pressure and circulating the refrigerant continuously, the system continuously discharges internal heat to an environment above the system temperature.

2. Kondensator

The function of the condenser is to cool the high-pressure, superheated refrigerant vapor discharged by the refrigerant compressor into a liquid refrigerant, and its heat is taken away by the cooling water. Dadurch kann der Kühlprozess kontinuierlich fortgesetzt werden.

3. Verdampfer

4. Thermostatische Expansionsventil (Kapillare)

The thermostatic expansion valve (capillary) is the throttling mechanism of the refrigeration system. Im Kühltrockner wird die Versorgung des Verdampferkältemittels und des Regulierungsbehörde durch den Drosselmechanismus realisiert. Der Drosselmechanismus ermöglicht die Kühlung, den Verdampfer aus der Hochtemperatur- und Hochdruckflüssigkeit zu betreten.

5. Wärmetauscher

The vast majority of refrigeration dryers have a heat exchanger, which is a heat exchanger that exchanges heat between air and air, generally a tubular heat exchanger (also known as a shell and tube heat exchanger). The main function of the heat exchanger in the refrigeration dryer is to “recover” the cooling capacity carried by the compressed air after being cooled by the evaporator, and use this part of the cooling capacity to cool the compressed air at a higher temperature carrying a large amount of water vapor (that is, the saturated compressed air discharged from the air compressor, cooled by the rear cooler of the air compressor, and then separated by air and water is Im Allgemeinen über 40 ° C), wodurch die Heizlast des Kühl- und Trocknungssystems verringert und den Zweck der Energieeinsparung erreicht wird. On the other hand, the temperature of low-temperature compressed air in the heat exchanger is recovered, so that the outer wall of the pipeline transporting compressed air does not cause “condensation” phenomenon due to the temperature below the ambient temperature. In addition, after the temperature of the compressed air rises, the relative humidity of the compressed air after drying is reduced (generally less than 20%), which is beneficial to prevent the rust of the metal. Some users (eg with air separation plants) need compressed air with low moisture content and low temperature, so the refrigeration dryer is no longer equipped with a heat exchanger. Da der Wärmetauscher nicht installiert ist, kann die kalte Luft nicht recycelt werden und die Wärmebelastung des Verdampfers erhöht sich stark. In this case, not only does the power of the refrigeration compressor need to be increased to compensate for energy, but also the other components of the entire refrigeration system (evaporator, condenser and throttling components) need to be increased accordingly. From the perspective of energy recovery, we always hope that the higher the exhaust temperature of the refrigeration dryer, the better (high exhaust temperature, indicating more energy recovery), and it is best that there is no temperature difference between the inlet and outlet. But in fact, it is not possible to achieve this, when the air inlet temperature is below 45 °C, it is not uncommon for the inlet and outlet temperatures of the refrigeration dryer to differ by more than 15 °C.

Druckluftverarbeitung

Wartung und Inspektion: Behalten Sie die Taupunkttemperatur des Kühltrockners über Null auf.

Um die Drucklufttemperatur zu reduzieren, muss die Verdunstungstemperatur des Kältemittels ebenfalls sehr niedrig sein. When the refrigeration dryer cools the compressed air, there is a layer of film-like condensate on the surface of the fin of the evaporator liner, if the surface temperature of the fin is below zero due to the decrease in the evaporation temperature, the surface condensate may freeze, at this time:

A. Due to the attachment of a layer of ice with a much smaller thermal conductivity on the surface of the inner bladder fin of the evaporator, the heat exchange efficiency is greatly reduced, the compressed air can not be fully cooled, and because of the insufficient heat absorption, the refrigerant evaporation temperature may be further reduced, and the result of such a cycle will inevitably bring many adverse consequences to the refrigeration system (such as “liquid Kompression “);

Prüfen

1. Die Druckdifferenz zwischen dem Einlass und Auslass von Druckluft liegt nicht über 0,035 mPa;

2. Verdunstungsdruckmesser 0,4 MPA-0,5 MPa;

3. Hochdruckstundenmesser 1,2 MPA-1.6mpa

4. Beobachten Sie häufig die Entwässerungs- und Abwassersysteme

Betriebsproblem

1 Überprüfen Sie vor dem Booten

1.1 Alle Ventile des Rohrnetzwerksystems befinden sich im normalen Standby -Zustand.

1.2 Das Kühlwasserventil ist geöffnet, der Wasserdruck sollte zwischen 0,15 und 0,4 mPa liegen und die Wassertemperatur unter 31ċ liegt.

1.3 Das Kältemittel Hochdruckmesser und das Niederdruckmesser des Kältemittels auf dem Armaturenbrett haben Anzeichen und sind im Grunde genommen gleich;

1.4 Überprüfen Sie die Stromversorgungsspannung, die 10% des Nennwerts nicht überschreiten darf.

2 Boot -Prozedur

2.1 Drücken Sie die Starttaste, der AC -Schütze verzögert sich um 3 Minuten und beginnt dann und der Kältemittel -Kompressor beginnt zu laufen.

2.2 Observe the dashboard, the refrigerant high-pressure meter should slowly rise to about 1.4Mpa, and the refrigerant low-pressure meter should slowly drop to about 0.4Mpa; Zu diesem Zeitpunkt hat die Maschine in den normalen Arbeitszustand eingegeben.

2.5 Überprüfen Sie, ob die Entwässerung des automatischen Abflusses normal ist.

2.6 Überprüfen Sie die Arbeitsbedingungen des Trockners regelmäßig, zeichnen Sie den Lufteinlass- und Auslassdruck, einen hohen und niedrigen Druck der kalten Kohle usw. auf.

3 Abschaltverfahren;

3.1 Schließen Sie das Auslassluftventil;

3.2 Schließen Sie das Einlassluftventil;

4 Vorsichtsmaßnahmen

4.1 Vermeiden Sie es, lange ohne Ladung zu laufen.

4.2 Starten Sie den Kältemittelkompressor nicht kontinuierlich, und die Anzahl der Starts und Stopps pro Stunde darf nicht mehr als 6 Mal betragen.

4.3 Um die Qualität der Gasversorgung zu gewährleisten, halten Sie sich unbedingt an die Reihenfolge des Startens und Stoppens.

4.3.1 Start: Lassen Sie den Trockner 3-5 Minuten lang laufen, bevor Sie den Luftkompressor oder das Einlassventil öffnen.

4.3.2 Herunterfahren: Schalten Sie zuerst den Luftkompressor oder das Auslassventil aus und schalten Sie dann den Trockner aus.

4.5 Der Luftdruck darf 0,95 MPa nicht überschreiten.

4.6 Die Einlasslufttemperatur überschreitet 45 Grad nicht.

4.7 Die Temperatur des Kühlwassers überschreitet 31 Grad nicht.

4.9 Die Zeitrelaiseinstellung im elektrischen Schaltschrank darf nicht weniger als 3 Minuten betragen.

4.10 Allgemeiner Betrieb, solange Sie die Tasten „Start“ und „Stopp“ steuern

4.11 The air-cooled refrigeration dryer cooling fan is controlled by the pressure switch, and it is normal for the fan not to turn when the refrigeration dryer works at a low ambient temperature. Mit zunehmender Hochdruck des Kältemittels beginnt der Lüfter automatisch.

 